Model for heat transfer at outside surfaces. Choice between
multiple models
Overview
The HeatTransferOutside is a model for the convective
heat transfer at outside walls
Concept
It allows the choice between three different models:
- after DIN 6946:
h = 4+4v , where
h (hCon) is the heat transfer coefficent
and v is the wind speed
- after the ASHRAE Fundamentals Handbook from 1989, the way it is
presented in EnergyPlus Engineering reference from 2011:
h
= D+Ev+Fv^2 , where h (hCon)
and v are as above and the coefficients
D, E, F depend on the surface of the
outer wall.
Attention: This is a
combined coefficient for convective and radiative heat
exchange.
- with a custom constant
h (hCon)
value
References
- DIN 6946 p.20
- ASHRAEHandbook1989, as cited in EnergyPlus Engineering
Reference. : EnergyPlus Engineering Reference, 2011 p.56
Example Results
AixLib.Utilities.Examples.HeatTransfer_test
AixLib.Utilities.Examples.HeatConv_outside
- November 16, 2016 by Ana Constantin:
Conditioned input WindSpeedPort and introduced protected input
WindSpeed_internal
- April 1, 2014 by Ana Constantin:
Uses components from MSL and respects the naming conventions
- March 30, 2012 by Ana Constantin:
Implemented.
Generated at 2026-04-15T18:18:36Z by OpenModelicaOpenModelica 1.26.3 using
GenerateDoc.mos