It is a dynamic model of modulating condensing boiler.
Hypothesis and equations
The gas consumption prediction model is estimated with a grey
box model. Electric consumption is determined according to the
consumption of the various operation phases of the boiler (purging,
pump, power on/off, standby, etc).
This model requires a limited amount of input data accessible
from the normative tests.
Following a sensitivity analysis,
- The durations of anti-short cycles (abnormally rapid start and
stop cycles), and especially the duration of the pump operation
after combustion have a very significant impact on consumption and
the number of machine cycles;
- The parameter Δη (representing the decrease in performance
depending on the load at a return of water temperature equal to
30°C) has nearly no effects on the results for the temperature
levels of the water law in question (between 35 and 45°C). In the
case of modelling a system requiring water temperatures higher than
35°C, the user can leave the default value, especially since this
parameter is not provided in the ATITA basis;
- Consideration of pre-combustion purge, during which the air in
combustion chamber must be renewed, has also a reduced impact:
over-consumption does not exceed 0.5% and is more due to a 30
second delay before launching the boiler than to the thermal power
lost in the smoke.
Bibliography
The model is configurable from certified data accessible in the
ATITA basis (rt2012-chauffage.com).
Instructions for use
none
Known limits / Use precautions
This is a detailed dynamic model. Some phenomena are represented
in a simple way:
- Heat losses through the wall are fully transmitted to the
environment (RT2012 gives the lost part coefficients -for example
through the wall for a wall boiler)
- The consumption of auxiliary is partially degraded in thermal
form (e.g. via the conversion of the water kinetic energy in pipes
into heat by friction for the power supplied to the pump), this
energy conservation is not considered now
Validations
Validated model - Hubert Blervaque, Sila Filfli 07/2013
--------------------------------------------------------------
Licensed by EDF under a 3-clause BSD-license
Copyright © EDF 2009 - 2023
BuildSysPro version 3.6.0
Author : Hubert BLERVAQUE, Sila FILFLI, EDF (2013)
--------------------------------------------------------------
Benoît Charrier 05/2015 : Suppression des connecteurs T &
m_flow.
Benoît Charrier 01/2016 : Passage du calcul du débit en equation
pour compatibilité OpenModelica.