recordParamsWTGT

Parameters

TypeNameDefaultDescription
Drive train control
Types.TimeHtTurbine Inertia in s (typical: 5 s)
Types.TimeHgGenerator Inertia in s (typical: 1 s)
Types.PerUnitDshaftDamping coefficient in pu (typical: 1.5 pu, base SNom, omegaNom)
Types.PerUnitKshaftSpring constant in pu (typical: 200 pu, base SNom, omegaNom)
Initialization
Types.AngularVelocityPuomegaRefWTGQ0PuStart value of reference angular frequency of torque control in pu (base omegaNom)