modelVariableImpedantFault

Variable impedant fault with R and X of the fault given by tables as functions of time

Extends from Dynawo.Electrical.Controls.Basics.SwitchOff.SwitchOffLine (Switch-off signal for a line).

Information

The variable impedant fault model enables making R and X of the fault vary through time. The values of R and X are entered with a combiTimeTable. The model is represented with the following equivalent circuit and conventions:


                I                  
   (terminal) -->-------R+jX------| Earth
                    

Parameters

TypeNameDefaultDescription
IntegerNbSwitchOffSignals (from SwitchOffLogic)Number of switch-off signals to take into account in inputs
BooleanSwitchOffSignal10 (from SwitchOffLogic)falseInitial switch-off signal 1
BooleanSwitchOffSignal20 (from SwitchOffLogic)falseInitial switch-off signal 2
BooleanSwitchOffSignal30 (from SwitchOffLogic)falseInitial switch-off signal 3
BooleanRunning0 (from SwitchOffLogic)if NbSwitchOffSignals >= 3 then not (SwitchOffSignal10 or SwitchOffSignal20 or SwitchOffSignal30) elseif NbSwitchOffSignals >= 2 then not (SwitchOffSignal10 or SwitchOffSignal20) else not SwitchOffSignal10Indicates if the component is initially running or not
Constants.stateState0 (from SwitchOffLine)Constants.state.ClosedStart value of connection state
StringImpedanceTableFile"NoName"Text file that contains the table to get the impedance from time
StringImpedanceTimeTable"NoName"Table to get the impedance from time : 3 columns, the first for time, second for R and third for X
Real[:,:]Tablefill(0.0, 0, 2)Table to get the impedance from time
BooleanTableOnFiletrueIf true, tables are defined on file or in function usertab

Connectors

TypeNameDefaultDescription
Modelica.Blocks.Interfaces.BooleanInputswitchOffSignal1 (from SwitchOffLogic)Switch-off signal 1
Modelica.Blocks.Interfaces.BooleanInputswitchOffSignal2 (from SwitchOffLogic)Switch-off signal 2
Modelica.Blocks.Interfaces.BooleanInputswitchOffSignal3 (from SwitchOffLogic)Switch-off signal 3
Modelica.Blocks.Interfaces.BooleanOutputrunning (from SwitchOffLogic)Indicates if the component is running or not
Dynawo.Connectors.ACPowerterminal

Components

TypeNameDefaultDescription
Constants.statestate (from SwitchOffLine)Line connection state
Types.ComplexImpedancePuZvPuThe complex variable representing the impedance of the fault
Modelica.Blocks.Sources.CombiTimeTableZvTimeTable