modelGeneratorPQPropDiagramPQSFR_INIT

Initialisation model for generator PQ with a PQ diagram, based on SignalN for the frequency handling, with a proportional reactive power regulation and that participates in the Secondary Frequency Regulation (SFR)

Extends from BaseClasses_INIT.BaseGeneratorSignalNPQDiagram_INIT (Base initialization model for SignalN generator models with PQ diagram), AdditionalIcons.Init.

Parameters

TypeNameDefaultDescription
Types.ComplexCurrentPuiStart0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Complex(0, 0)Start value of complex current at terminal in pu (base UNom, SnRef) (receptor convention)
Types.ActivePowerPuP0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Start value of active power at terminal in pu (base SnRef) (receptor convention)
Types.ReactivePowerPuQ0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Start value of reactive power at terminal in pu (base SnRef) (receptor convention)
Types.VoltageModulePuU0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Start value of voltage amplitude at terminal in pu (base UNom)
Types.AngleUPhase0 (from BaseGeneratorSignalNPQDiagram_INIT)Start value of voltage angle at terminal in rad
Types.ActivePowerPuPMax (from BaseGeneratorSignalNPQDiagram_INIT)Maximum active power in MW
Types.ActivePowerPuPMin (from BaseGeneratorSignalNPQDiagram_INIT)Minimum active power in MW
Types.ReactivePowerPuQMax0 (from BaseGeneratorSignalNPQDiagram_INIT)Start value of maximum reactive power in Mvar
Types.ReactivePowerPuQMin0 (from BaseGeneratorSignalNPQDiagram_INIT)Start value of minimum reactive power in Mvar

Connectors

TypeNameDefaultDescription
Dynawo.Connectors.ActivePowerPuOutputPGen0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Start value of active power at terminal in pu (base SnRef) (generator convention)
Dynawo.Connectors.ReactivePowerPuOutputQGen0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Start value of reactive power at terminal in pu (base SnRef) with limits (generator convention)
Dynawo.Connectors.VoltageModulePuOutputU0PuVar (from BaseGeneratorSignalNPQDiagram_INIT)Start value of voltage amplitude at terminal in pu (base UNom)
Dynawo.Connectors.ComplexVoltagePuOutputu0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Start value of complex voltage at terminal in pu (base UNom)
Dynawo.Connectors.ComplexCurrentPuOutputi0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Start value of complex current at terminal in pu (base UNom, SnRef) (receptor convention)
Modelica.Blocks.Interfaces.BooleanOutputlimUQDown0 (from BaseGeneratorSignalNPQDiagram_INIT)Whether the minimum reactive power limits are reached or not (from generator voltage regulator), start value
Modelica.Blocks.Interfaces.BooleanOutputlimUQUp0 (from BaseGeneratorSignalNPQDiagram_INIT)Whether the maximum reactive power limits are reached or not (from generator voltage regulator), start value

Components

TypeNameDefaultDescription
Types.ReactivePowerPuQGenRaw0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Start value of reactive power at terminal in pu (base SnRef) (generator convention)
Types.ComplexApparentPowerPus0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Start value of complex apparent power at terminal in pu (base SnRef) (receptor convention)
Types.ActivePowerPuPMaxPu (from BaseGeneratorSignalNPQDiagram_INIT)Maximum active power in pu (base SnRef)
Types.ActivePowerPuPMinPu (from BaseGeneratorSignalNPQDiagram_INIT)Minimum active power in pu (base SnRef)
Types.ReactivePowerPuQMax0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Start value of maximum reactive power in pu (base SnRef)
Types.ReactivePowerPuQMin0Pu (from BaseGeneratorSignalNPQDiagram_INIT)Start value of minimum reactive power in pu (base SnRef)
QStatusqStatus0 (from BaseGeneratorSignalNPQDiagram_INIT)Start voltage regulation status: standard, absorptionMax or generationMax