recordBaseParameters

Information

In this file, you should declare : 
- SNom of the plant being simulated (this won't change much as everything is in pu)
- XaPu and XbPu, stability impedances defined in the french grid code and provided in every connection project's requirement document.

Parameters

TypeNameDefaultDescription
Types.ApparentPowerModuleSNom35Nominal apparent power in MVA
Types.PerUnitXaPu0.05*Electrical.SystemBase.SnRef/SNomReactance a of the DTR in pu (base SnRef, UNom)
Types.PerUnitXbPu0.3*Electrical.SystemBase.SnRef/SNomReactance b of the DTR in pu (base SnRef, UNom)
Types.ActivePowerPuP0Pu-1*SNom/Electrical.SystemBase.SnRefStart value of active power at regulated bus in pu (receptor convention) (base SnRef)
Types.ReactivePowerPuQ0Pu0*SNom/Electrical.SystemBase.SnRefStart value of reactive power at regulated bus in pu (receptor convention) (base SnRef)
Types.VoltageModulePuU0Pu1Start value of voltage magnitude at regulated bus in pu (base UNom)
Types.VoltageModulePuUInfPusqrt((P0Pu*XccPu)^2 + (Q0Pu*XccPu + U0Pu^2)^2)/U0PuValue of voltage magnitude at infinite in pu (base UNom)
Types.AngleUPhase0Modelica.Math.atan2(-P0Pu*XccPu, Q0Pu*XccPu + U0Pu^2)Start value of voltage phase angle at regulated bus in rad
Types.PerUnitXccPuReactance of equivalent branch connection to the grid in pu (base SnRef, UNom)