This model applies an energy balance on the cover. The
energy balance is done by taking into account:
- Sensible heat flows (i.e. all the flows connected to
the heat port). These should be the sensible heat caused by
convection is mainly exhanged with the air (top air zone when the
screen is drawn, main air zone in the absence of a thermal screen)
and the outside air; and long-wave radiation is exchanged with the
heating pipes, the canopy, the floor, the thermal screen and the
sky.
- Latent heat flows associated with condensation of
moisture. In fact, depending on the water vapor pressure
difference, condensation may take place at the inner side of the
cover. Evaporation of moisture from the cover to the air is
neglected because in greenhouses, condensate on the cover is
commonly drained. The latent heat flows are determined by
multiplying the moisture flows at the vapor mass port to the latent
heat of vaporization
- Short-wave radiation absorbed from the sun (i.e. the
forced flow from the short-wave radiation input).
Because the properties of the cover are parameters of
the model, the user has the possibility to adapt the model for any
type of cover (single-glass, double-glass, plastic,
etc.).
Since glass thickness is commonly small (i.e. 4mm),
conduction through the cover is neglected. The vapor pressure of
water at the cover is defined by the saturated vapor pressure for
its temperature.