This model describes the mass flow rate and pressure difference relation of an orifice in the form
V_flow = k * dp^m,
where k is a variable and m a
parameter. For turbulent flow, set m=1/2 and for
laminar flow, set m=1.
The model is used as a base for the interzonal air flow models.
A because IBPSA.Airflow.Multizone.EffectiveAirLeakageArea
uses the effective leakage area L rather than
A.v=V_flow/A as parameter
A has been removed.lWet as this is only used to compute
the Reynolds number, and the Reynolds number is not used by this
model. Also removed the variable Re for the Reynolds
number.final allowFlowReversal=true. See #877.showDesignFlowDirection in extends
statement. This is for #349.mExc as
Modelica.SIunits.Mass sets min=0, but
mExc can be negative.useConstantDensity to
useDefaultProperties and also applied the parameter to
the computation of the dynamic viscosity. The conversion script can
be used to update this parameter.sta_a, as this
may be conditionally removed and hence it is not proper Modelica
syntax to use it outside of a connect statement.mExc to avoid
error when checking model in pedantic mode with Dymola 2014.fixed=false attribute of protected parameter
k.