Partial interface for a generic controller
Description
Partial interface for a continuous/discrete time
controller.
The model has the following ports
| Name |
Description |
Conditional? |
| SP |
Set Point |
NO |
| PV |
Process Variable |
NO |
| CS |
Control Signal |
NO |
| TR |
Track Reference signal |
YES (useTS) |
| TS |
Track Switch signal |
YES (useTS) |
| Bias |
Biasing signal |
YES (useBIAS) |
| ATreq |
AutoTuning request |
YES (useAT) |
And some of them can be conditionally selected, by specifying a
boolean flag.
AntiWindUp mode
If the boolean flag AntiWindup is tue
the output of the block ( CS )
saturates at the values specified by CSmin and CSmax.
Tracking mode
If the boolean flag useTS, the inputs
TS and TR
are enabled.
When enabled, if the TS signal is true
the output CS is forced to follow the
track reference signal TR.
Discretisation
For each controller is defined a sampling time Ts and a coefficient alpha.
The discretisation of the continuos time transfer function has been
performed with the bilinear transformation formula
z - 1
s = ------------------------------
z*alpha*Ts - (alpha - 1)*Ts
that is equivalent to
- Forward Euler (FE) if
alpha = 0
- Backward Euler (BE) if
alpha = 1
- Tustin (TU) if
alpha = 0.5
- Industrial Control Systems (v 1.0.0) : April-May 2012
-
- List of revisions:
-
- 11 May 2012 (author: Marco Bonvini)
- Main Authors:
- Marco Bonvini; <bonvini@elet.polimi.it>
- Alberto Leva <leva@elet.polimi.it>
- Politecnico di Milano
- Dipartimento di Elettronica e Informazione
- Via Ponzio 34/5
- 20133 Milano - ITALIA -
- Copyright:
- Copyright © 2010-2012, Marco Bonvini and Alberto
Leva.
- The IndustrialControlSystems package is free
software; it can be redistributed and/or modified under the terms
of the Modelica license.
Generated at 2026-04-14T18:18:34Z by OpenModelicaOpenModelica 1.26.3 using