Information

Discrete implementation of Tap-Changing Under Load (TCUL) transformer according to
method D1-D4 using a state-machine implementation of the control system and
tap changer mechanism. See documentation for 'Controllers.TCULDiscrete' for
documentation on the control system.
Note that the tap position of a discrete tap changer is not properly
initialized by the initial value solver in Dymola version 4.0c.
This can by manually by adding e.g., the string: Controller(tappos(start=8))
in the 'Modifiers' field (initializes the tap to position 8).

Parameters

TypeNameDefaultDescription
ObjectStab.Base.ResistanceR (from ImpTransformer)0.0Leakage Resistance
ObjectStab.Base.ReactanceX (from ImpTransformer)0.1Leakage Reactance
ObjectStab.Base.TapRation1Transformer Ratio

Connectors

TypeNameDefaultDescription
ObjectStab.Base.PinT1 (from TwoPin)
ObjectStab.Base.PinT2 (from TwoPin)

Components

TypeNameDefaultDescription
ObjectStab.Network.IdealTransformerTr (from ImpTransformer)
ObjectStab.Network.ImpedanceImp (from ImpTransformer)
ObjectStab.Network.Controllers.TCULDiscreteController
ObjectStab.Base.VoltageMeasurementPrimaryVoltage
ObjectStab.Base.VoltageMeasurementSecondaryVoltage