This model demonstrates the correct
behaviour of the LeadMOrderLag filter in two cases, by comparing its ouptut to the
analytical response.
The first case is a simple
lead-lag filter with k = 10, T1 = 4, T2 = 2 and M = 1.
The second case is a filter
with k = 1, T1 = 1e-5 (very small, practically zero), T2 = 1/100
and N = 100, which is the (0,100) Padé approximation of a pure time
delay of 1 second.