modelExample_11_1_Area
Incropera and DeWitt Example 11.1: heat transfer area from the heat rate (LMTD_HX_A)
Extends from TRANSFORM.Icons.Example (Icon for runnable examples).
Information
Example 11.1 (pp. 680-682) of Fundamentals of Heat and Mass Transfer by Incropera and DeWitt: a counterflow, concentric tube heat exchanger cools engine oil (side 1, 0.1 kg/s, 100 °C to 60 °C) with water (side 2, 0.2 kg/s, 30 °C in). The book uses constant specific heats (oil 2131 J/(kg.K), water 4178 J/(kg.K)) and finds q = 8524 W, a water outlet temperature of 40.2 °C, a log mean temperature difference of 43.2 K and, with U = 38.1 W/(m2.K), a heat transfer area of 5.178 m2.
LMTD_HX_A is given the heat rate and the heat transfer coefficients and returns the heat transfer area. The book gives only the overall coefficient U, so each side is given 2U here.
Components
| Type | Name | Default | Description |
|---|---|---|---|
| TRANSFORM.Fluid.BoundaryConditions.MassFlowSource_T | boundary_a1 | Oil inlet | |
| TRANSFORM.Fluid.BoundaryConditions.Boundary_pT | boundary_b1 | Oil outlet | |
| TRANSFORM.Fluid.BoundaryConditions.MassFlowSource_T | boundary_a2 | Water inlet | |
| TRANSFORM.Fluid.BoundaryConditions.Boundary_pT | boundary_b2 | Water outlet | |
| TRANSFORM.HeatExchangers.LMTD_HX_A | lmtd_HX | alpha_1 = alpha_2 = 2*U gives the book's U = 38.1 W/(m2.K) | |
| TRANSFORM.Utilities.ErrorAnalysis.UnitTests | unitTests | Reference values are the book's answers |
Contents
| Name | Description |
|---|---|
| Hot side: engine oil, cp as in the book | |
| Cold side: water, cp as in the book |