modelExample_11_1_UA

Incropera and DeWitt Example 11.1: thermal conductance UA from the heat rate (LMTD_HX_UA)

Extends from TRANSFORM.Icons.Example (Icon for runnable examples).

Information

Example 11.1 (pp. 680-682) of Fundamentals of Heat and Mass Transfer by Incropera and DeWitt: a counterflow, concentric tube heat exchanger cools engine oil (side 1, 0.1 kg/s, 100 °C to 60 °C) with water (side 2, 0.2 kg/s, 30 °C in). The book uses constant specific heats (oil 2131 J/(kg.K), water 4178 J/(kg.K)) and finds q = 8524 W, a water outlet temperature of 40.2 °C, a log mean temperature difference of 43.2 K and, with U = 38.1 W/(m2.K), a heat transfer area of 5.178 m2.

LMTD_HX_UA is given the heat rate and returns the thermal conductance UA (the book's U times A).

Components

TypeNameDefaultDescription
TRANSFORM.Fluid.BoundaryConditions.MassFlowSource_Tboundary_a1Oil inlet
TRANSFORM.Fluid.BoundaryConditions.Boundary_pTboundary_b1Oil outlet
TRANSFORM.Fluid.BoundaryConditions.MassFlowSource_Tboundary_a2Water inlet
TRANSFORM.Fluid.BoundaryConditions.Boundary_pTboundary_b2Water outlet
TRANSFORM.HeatExchangers.LMTD_HX_UAlmtd_HX
TRANSFORM.Utilities.ErrorAnalysis.UnitTestsunitTestsReference values are the book's answers

Contents

NameDescription
Medium_oilHot side: engine oil, cp as in the book
Medium_waterCold side: water, cp as in the book