Test case for Water.Flow1DFV
The model is designed to test the component
Water.Flow1DFV (fluid side of a heat exchanger, finite
volumes).
This model represent the fluid side of a heat exchanger with an
applied external heat flow. The operating fluid is liquid
water.
During the simulation, the inlet specific enthalpy, heat flux
and mass flow rate are changed. The outlet temperature can be
predicted analytically assuming incompressible flow and constant
cp.
- t=0 s, Step variation of the specific enthalpy of the fluid
entering the heat exchanger. The outlet temperature should undergo
a step increase of 10 degrees 10 s later.
- t=30 s, Step variation of the thermal flow entering the heat
exchanger lateral surface. The outlet temperature should undergo a
ramp increase of 10 degrees lasting 10 s
- t=50 s, Step reduction of the mass flow rate entering the heat
exchanger. The outlet temperature should undergo a ramp change of
one degree lasting 10s
Simulation Interval = [0...80] sec
Integration Algorithm = DASSL
Algorithm Tolerance = 1e-6