The model is designed to test the generator and load components
of the Electrical
library.
Simulation sequence:
- t=0 s: The system starts at equilibrium
- t=1 s: The torque is brought to zero. Since there is a deficit
of 100% nominal power in the island, the frequency starts
decreasing with a rate of 100% for each acceleration time Ta=10 s,
i.e., by 10%/s, or 5 Hz/s
Since the system is not connected to a grid, the generator has
referenceGenerator =
true to provide a well-posed initialization problem.
Simulation Interval = [0...2] sec
Integration Algorithm = DASSL
Algorithm Tolerance = 1e-6