.TransiEnt.Components.Electrical.Machines

Eletric Machines (asynchronous and synchronous generators and motors)

Information

This documnentation wants to give a short overview which machine model can be used for different applications.

When using the ActivePowerPort, the synchron generator is represented by the ActicePowerGenerator. For special applicants where net and rotation frequencies are decoupled, use the VariableSpeedActivePowerGenerator.

When using the ApparentPowerPort, Use the LinearSynchronousMachine.

The ComplexPowerPort is the most advanced power port in the TransiEnt Library. Firstly, with this power port it is necessary to have exactly one reference. This is done by the slack versions (IsSlack=true) of the machines.

The LinearSynchronous is the simplest model. It only models frequency andactive power dynamics. The voltage is fixed. Reactive power can be distributed freeely.

The models SynchronousMachineComplex and TwoAxisSynchronousMachineComplex machine are stationary model which should only be used for small disturbances. The SynchronousMachineComplex can only describe cylindrical rotor machines.

These and the following models need a voltage controller which generates the exciation voltage as input.

The transient and subtransient versions of the machines are the most advanced models for dynamic simulations. The considered time domains are given in the model documentations of the models.

The Models for the ComplexPowerPort can operate with more than one rotation frequency for considering angle stability and power oscilations

Please set the voltage angle reference to the polar wheel voltage of the slack generator (simCenter.use_reference_polar_wheel=true) when using more than one frequency. By Default the voltage at the slack genertor's ports is the voltage angle reference.

Motor models should be used as motors in general, although they allow mechanical power in both directions.

Short description by Jan-Peter Heckel (jan.heckel@tuhh.de), Apr 2018

Description competet in Nov 2018

Contents

Name Description
 Base
 ExcitationSystemsVoltageController Package for different excitation systems and voltage controller
 Check
 ActivePowerGenerator ActicePowerPort: Static machine model with constant effiency
 VariableSpeedActivePowerGenerator ActicePowerPort: Static machine model with torque control for the shaft speed
 MSLSynchronousMachine ApparentPowerPort: Transient MSL synchronous machine model to TransiEnt interfaces
 LinearSynchronousMachine ApparentPowerPort: Linear generator model with constant efficiency
 LinearSynchronousMachineComplex ComplexPowerPort: Linear generator model with constant efficiency
 SynchronousMachineComplex ComplexPowerPort: SM model with electric circuit, excitation voltage input
 TwoAxisSynchronousMachineComplex ComplexPowerPort: Stationary Two-Axis SM model with excitation voltage input
 TwoAxisSynchronousMachineComplexTransient ComplexPowerPort: Transient Two-Axis SM model with excitation voltage input
 TwoAxisSynchronousMachineComplexSubtransient ComplexPowerPort: Subtransient Two-Axis SM model with excitation voltage input
 MotorComplex simple electrical motor model for unspecified motor type
 InductionMotorComplex_L1E Model of Induction Motor for ComplexPowerPort
 InductionMotorComplex_L3E Model of Induction Motor for ComplexPowerPort
 InductionMotorSimple Induction Motor Model with improved coupling and simple equations