Chiller staging control logic
This is a chiller staging control that works as follows:
- The chillers are all off when cooling mode is Free
Cooling.
- One chiller is commanded on when cooling mode is not Free
Cooling.
- Two chillers are commanded on when cooling mode is not Free
Cooling and the cooling load addressed by each chiller is larger
than a critical value.
- September 11, 2017, by Michael Wetter:
Revised switch that selects the operation mode for issue
921
- July 30, 2017, by Yangyang Fu:
First implementation.