Staging control for constant speed pumps
This model describes a simple staging control for two
constant-speed pumps in a chilled water plant with two chillers and
a waterside economizer (WSE). The staging sequence is shown as
below.
- When WSE is enabled, all the constant speed pumps are commanded
on.
- When fully mechanical cooling (FMC) mode is enabled, the number
of running constant speed pumps equals to the number of running
chillers.
- September 3, 2024, by Jianjun Hu:
Added plant on signal to pumps control. This is for issue
3989.
- September 11, 2017, by Michael Wetter:
Revised switch that selects the operation mode for issue
921.
- September 2, 2017, by Michael Wetter:
Changed implementation to use Buildings.Applications.DataCenters.Types.CoolingModes.
- July 30, 2017, by Yangyang Fu:
First implementation.