Mode controller for integrated waterside economizer and chiller
Controller that outputs if the chilled water system is in Free
Cooling (FC) mode, Partially Mechanical Cooling (PMC) mode or Fully
Mechanical Cooling (FMC) mode.
The waterside economizer is enabled when
- The waterside economizer has been disabled for at least 20
minutes, and
- TCHWR > TWetBul +
TTowApp + deaBan1
The waterside economizer is disabled when
- The waterside economizer has been enabled for at least 20
minutes, and
- TWSE_CHWST > TWSE_CHWRT -
deaBan2
The chiller is enabled when
- The chiller has been disabled for at leat 20 minutes, and
- TWSE_CHWST > TCHWSTSet +
deaBan3
The chiller is disabled when
- The chiller has been enabled for at leat 20 minutes, and
- TWSE_CHWST ≤ TCHWSTSet +
deaBan4
where TWSE_CHWST is the chilled water supply
temperature for the WSE, TWetBul is the wet bulb
temperature, TTowApp is the cooling tower
approach, TWSE_CHWRT is the chilled water return
temperature for the WSE, and TCHWSTSet is the
chilled water supply temperature setpoint for the system. deaBan
1-4 are deadbands for each switching point.
References
- Stein, Jeff. Waterside Economizing in Data Centers: Design and
Control Considerations. ASHRAE Transactions 115.2 (2009).
- July 24, 2017, by Yangyang Fu:
First implementation.