Controller for the fan speed in cooling towers
This model describes a simple cooling tower speed controller for
a chilled water system with integrated waterside economizers.
The control logics are described in the following:
- When the system is in Fully Mechanical Cooling (FMC) mode, the
cooling tower fan speed is controlled to maintain the condener
water supply temperature (CWST) at or around the setpoint.
- When the system is in Partially Mechanical Cooling (PMC) mode,
the cooling tower fan speed is set as 100% to make condenser water
as cold as possible and maximize the waterside economzier
output.
- When the system is in Free Cooling (FC) mode, the cooling tower
fan speed is controlled to maintain the chilled water supply
temperature (CHWST) at or around its setpoint.
- July 30, 2017, by Yangyang Fu:
First implementation.
Generated at 2026-04-15T18:18:36Z by OpenModelicaOpenModelica 1.26.3 using