Model that implements an on and off controller for a reheater
This model can be used to generate on/off signal for the
reheater inside the AHU.
This reheater will be on only if the following two conditions
are satisfied at the same time:
- The position of the water-side valve reaches its switch point,
yValSwi;
- The difference between the inlet temperature of the reheater
and the required outlet temperature setpoint is lower than its
critical switch point,
dTSwi.
In addition, a deadband and waiting time is used to avoid
frequent switching.
- September 12, 2017 by Yangyang Fu:
First implementation.