Outdoor air and return air damper position limits for units with
separated minimum outdoor air damper and airflow measurement
Block that outputs the position limits of the return and outdoor
air damper for units with a separated minimum outdoor air damper
and airflow measurement. It is implemented according to Section
5.16.5 of the ASHRAE Guideline 36, May 2020.
Minimum outdoor air set point
Calculate the outdoor air set point with
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.
Minimum outdoor air control loop
Minimum outdoor air control loop is enabled when the supply fan
is proven ON (u1SupFan=true) and in occupied mode, and
disabled and output set to zero otherwise
The minimum outdoor airflow rate shall be maintained at the
minimum outdoor air set point by a reverse-acting control loop
whose output is 0% to 100%. From 0% to 50% loop output, the minimum
outdoor air damper is opened from 0%
(minOutDamPhy_min) to 100%
(minOutDamPhy_max).
Return air damper
- Return air damper minimum outdoor air control is enabled when
the minimum outdoor air damper is fully open and the economizer
outdoor air damper is less than a projected position limit, which
is 5% when supply fan speed is at 100% design speed proportionally
up to 80% when the fan is at minimum speed.
- Return air damper minimum outdoor air control is disabled when
the minimum outdoor air damper is not fully open or the economizer
outdoor air damper is 10% above the projected position limit as
determined above.
- When enabled, the maximum return air damper set point is
reduced from 100% (
retDamPhy_max) to 0%
(retDamPhy_min) as the minimum outdoor air loop output
rises from 50% to 100%.
- August 1, 2020, by Jianjun Hu:
First implementation.