This sequence outputs AHU level uncorrected minimum outdoor
airflow rate VUncOutAir_flow and effective minimum
outdoor airflow rate VEffOutAir_flow when complying
with ASHRAE Standard 62.1 ventilation requirements. It is
implemented according to Section 5.16.3.1 of ASHRAE Guideline G36,
May 2020.
It requires following inputs which are sum or maximum of the outputs from the zone level calculation. See Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.ASHRAE62_1.SumZone for these inputs.
VSumAdjPopBreZon_flow.VSumAdjAreBreZon_flow.VSumZonPri_flow.uOutAirFra_max.The calculation is done using the steps below.
VUncDesOutAir_flow and
VDesTotOutAir_flow.VUncOutAir_flow is recalculated continuously based on
the adjusted population and area component breathing zone flow rate
of the zones being served determined in accordance with Section
5.2.1.3. See
Buildings.Controls.OBC.ASHRAE.G36.VentilationZones.ASHRAE62_1.Setpoints.
VUncOutAir_flow = min(VUncDesOutAir_flow, (VSumAdjPopBreZon_flow + VSumAdjAreBreZon_flow))
sysVenEff = 1 + (VUncOutAir_flow/VSumZonPri_flow) - uOutAirFra_max
VEffOutAir_flow as the uncorrected outdoor air intake
divided by the system ventilation efficiency, but no larger than
the design total outdoor airflow rate
VDesTotOutAir_flow:
VEffOutAir_flow = min(VUncOutAir_flow/sysVenEff, VDesTotOutAir_flow)