This sequence sums up zone level minimum outdoor airflow setpoints when complying with California Title 24 ventilation requirements. It is implemented according to Section 5.16.3.2 of ASHRAE Guideline G36, May 2020.
It calculates following values:
VZonAbsMin_flow for all zones in all zone groups that
are in occupied mode.VZonDesMin_flow for all zones in all zone groups that
are in occupied mode.yMaxCO2.See the zone absolute and design minimum outdoor airflow
setpoint VZonAbsMin_flow and
VZonDesMin_flow from
Buildings.Controls.OBC.ASHRAE.G36.VentilationZones.Title24.Setpoints
for the detailed description.