Sequence for controlling group of relief fans and their dampers for AHUs using actuated relief dampers with relief fan(s). It is developed based on Section 5.16.9 of ASHRAE Guideline 36, May 2020.
u1SupFan=true), and shall be disabled
otherwise.dpBui) shall be time
averaged with a sliding 5-minute window and 15 second sampling rate
(to dampen fluctuations). The average value shall be that displayed
and used for control.dpBuiSet) of 12 Pa (0.05 in. of water) with an
output ranging from 0% to 100%. The loop is disabled and output set
to zero when all fans in the relief system group are disabled.relFanSpe_min) plus 15%, start stage-up timer. Each
time the timer reaches 7 minutes, start the next relief fan (and
open the associated damper) in the relief system group, per staging
order, and reset the timer to 0. The timer is reset to 0 and frozen
if control loop is below minimum speed plus 15%. Note, when staging
from Stage 0 (no relief fans) to Stage 1 (one relief fan), the
discharge dampers of all nonoperating relief fans must be
closed.relFanSpe_min), start stage-down timer. Each time the
timer reaches 5 minutes, shut off lag fan per staging order and
reset the timer to 0. The timer is reset to 0 and frozen if PID
loop rises above minimum speed or all fans are OFF. If all fans are
OFF, go to Stage 0 (all dampers open and all fans OFF).displayUnit.