Return fan control for AHUs using return fan with airflow tracking
Sequence for controlling return fan yRetFan for
AHUs using return fan with airflow tracking. It is implemented
according to Section 5.16.11 of ASHRAE Guideline G36, May 2020.
- Return fan operates whenever associated supply fan is proven on
(
u1SupFan = true).
- Return fan speed shall be controlled to maintain return airflow
equal to supply airflow less differential
difFloSet,
as determined per section 3.2.1.5.
- Relief or exhaust dampers shall be enabled when the associated
supply and return fans are proven on and closed otherwise. Exhaust
dampers shall modulate as the inverse of the return air damper per
section 5.16.2.3. This is implemented in
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.Modulations.ReturnFan
- May 20, 2021, by Jianjun Hu:
First implementation.