Supply fan control for a multi zone VAV AHU according to Section 5.16.1 of ASHRAE Guideline G36, May 2020.
Static pressure setpoint shall be reset using trim-respond logic using following parameters as a starting point:
| Variable | Value | Definition |
|---|---|---|
| Device | AHU Supply Fan | Associated device |
| SP0 | iniSet |
Initial setpoint |
| SPmin | minSet |
Minimum setpoint |
| SPmax | maxSet |
Maximum setpoint |
| Td | delTim |
Delay timer |
| T | samplePeriod |
Time step |
| I | numIgnReq |
Number of ignored requests |
| R | uZonPreResReq |
Number of requests |
| SPtrim | triAmo |
Trim amount |
| SPres | resAmo |
Respond amount |
| SPres_max | maxRes |
Maximum response per time interval |
Supply fan speed is controlled with a PI controller to maintain
duct static pressure at setpoint when the fan is proven on. The
setpoint for the PI controller and the measured duct static
pressure are normalized with the maximum design static presssure
maxSet. Where the zone groups served by the system are
small, provide multiple sets of gains that are used in the control
loop as a function of a load indicator (such as supply fan airflow
rate, the area of the zone groups that are occupied, etc.).