This block outputs the cooling coil control signal if the fan is
on and the zone is in cooling status (see Buildings.Controls.OBC.ASHRAE.G36.Types.ZoneStates).
Otherwise, the control signal for the coil is set to
0. The implementation is according to the Section
5.18.5.3 of ASHRAE Guideline 36, May 2020.