Freeze protection sequence for single zone air handling unit
Freeze protection sequence for single zone AHU system. It is
developed based on Section 5.18.11 of ASHRAE Guideline 36, May
2020.
- If the supply air temperature
TAirSup drops below
4 °C (40 °F) for 5 minutes, send two (or more, as required to
ensure that heating plant is active, minHotWatReq)
heating hot-water plant requests, override the outdoor air damper
to the minimum position, and modulate the heating coil to maintain
a suppy air temperature of at least 6 °C (42 °F). Disable this
function when supply air temperature rises above 7 °C (45 °F) for 5
minutes.
- If the supply air temperature
TAirSup drops below
3 °C (38 °F) for 5 minutes, fully close both the economizer damper
and the minimum outdoor air damper for 1 hour and set a Level 3
alarm noting that minimum ventilation was interrupted. After 1
hour, the unit shall resume minimum outdoor air ventilation and
enter the previous stage of freeze protection.
- If it is warm enough that the supply air temperature rises
above 7 °C (45 °F) with minimum ventilation, the unit will remain
in Stage 1 freeze protection for 5 minutes then resume normal
operation.
- Upon signal from the freeze-stat (if installed), or if supply
air temperature drops below 3 °C (38 °F) for 15 minutes or below 1
°C (34 °F) for 5 minutes, shut down supply and return (or relief)
fan(s), close outdoor air damper, open the cooling-coil valve to
100%, and energize the CHW pump system. Also send two (or more, as
required to ensure that heating plant is active,
minHotWatReq) heating hot-water plant requests,
modulate the heating coil to maintain the higher of the supply air
temperature or the mixed air temperature at 27 °C (80 °F), and set
a Level 2 alarm indicating the unit is shut down by freeze
protection.
- If a freeze-protection shutdown is triggered by a low air
temperature sensor reading, it shall remain in effect until it is
reset by a software switch from the operator's workstation. (If a
freeze-stat with a physical reset switch is used instead, there
shall be no software reset switch.)
- March 1, 2023, by Michael Wetter:
Changed constants from 0 to 0.0 and
1 to 1.0.
This is for
#3267.
- December 22, 2022, by Jianjun Hu:
Added flag to disable freeze protection.
This is for issue
3139.
- July 15, 2021, by Jianjun Hu:
First implementation.
Generated at 2026-04-15T18:18:36Z by OpenModelicaOpenModelica 1.26.3 using
GenerateDoc.mos