This sequence outputs the system reset requests for single zone air handling unit. The implementation is according to the Section 5.18.15 of ASHRAE Guideline 36, May 2020.
yChiWatResReqTAirSup exceeds the
cooling supply air temperature set point TSupCoo by 3
°C (5 °F) for 2 minutes, send 3 requests.TAirSup exceeds the
cooling supply air temperature set point TSupCoo by 2
°C (3 °F) for 2 minutes, send 2 requests.uCooCoi_actual is greater than 95%, send 1 request
until the uCooCoi_actual is less than 85%.uCooCoi_actual is less than 95%, send 0 request.yChiPlaReqSend the chiller plant that serves the system a chiller plant request as follows:
uCooCoi_actual
is greater than 95%, send 1 request until the
uCooCoi_actual is less than 10%.uCooCoi_actual is less than 95%, send 0 request.yHotWatResReqTAirSup is 17 °C (30
°F) less than the heating supply air temperature set point
TSupHeaEco for 5 minutes, send 3 requests.TAirSup is 8 °C
(15 °F) less than the heating supply air temperature set point
TSupHeaEco for 5 minutes, send 2 requests.uHeaCoi_actual is greater than 95%, send 1 request
until the uHeaCoi_actual is less than 85%.uHeaCoi_actual is less than 95%, send 0 request.yHotWatPlaReqSend the heating hot-water plant that serves the air handling unit a heating hot-water plant request as follows:
uHeaCoi_actual is
greater than 95%, send 1 request until the hot water valve position
is less than 10%.uHeaCoi_actual is
less than 95%, send 0 requests.