Sequence for controlling actuated relief damper
yRelDam for AHUs using actuated relief damper without
a fan. It is implemented according to Section 5.18.8 of ASHRAE
Guideline G36, May 2020.
In Section 3.2.2.3, find the relief damper position setpoint limits:
relDam_min: the relief damper position that
maintainx a building pressure of 12 Pa (0.05 in. of water) while
the economizer is positioned to provide minimum outdoor airflow
while the supply fan is at minimum speed.relDam_max: the relief damper position that
maintainx a building pressure of 12 Pa (0.05 in. of water) while
the economizer damper is fully open and the fan speed is at cooling
maximum.Relief damper shall be enabled when the associated supply fan is proven on and any outdoor air damper is open, and disabled and closed otherwise.
Relief damper position shall be reset lineary from
relDam_min to relDam_max as the commanded
economizer damper position goes from uOutDam_min to
100% open.