Sequence for control of relief fan in AHU
Sequence for controling relief fan that is part of AHU. It is
developed based on Section 5.16.9 of ASHRAE Guideline 36, May 2020,
with the modification to accommodate the single relief fan
control.
- The relief fan shall be enabled when the AHU supply fan is
proven ON (
u1SupFan=true), and shall be disabled
otherwise.
- Building static pressure (
dpBui) shall be time
averaged with a sliding 5-minute window and 15 second sampling rate
(to dampen fluctuations). The average value shall be that displayed
and used for control.
- A P-only control loop maintains the building pressure at a set
point (
dpBuiSet) of 12 Pa (0.05 in. of water) with an
output ranging from 0% to 100%. The loop is disabled and output set
to zero when the relief fan is disabled.
- Fan speed shall be equal to the PID signal but no less than the
minimum speed.
- When relief system is enabled, and the control loop output is
above 5%, open the motorized dampers to the relief fans; close the
dampers when the loop output drops to 0% for 5 minutes.
- When the control loop output is above minimum speed
(
relFanSpe_min) plus 15% by 7 minutes, start the
relief fan.
- When the control loop output is below minimum speed
(
relFanSpe_min) by 5 minutes, shut off the relief
fan.
- March 5, 2024, by Michael Wetter:
Corrected wrong use of displayUnit.
- September 20, 2022, by Jianjun Hu:
First implementation.