This model uses the base energy transfer station defined in Buildings.DHC.ETS.Combined.BaseClasses.PartialHeatPumpHeatExchanger.
Domestic hot water is produced using a dedicated water-to-water heat pump with storage tank.
Heating is enabled based on the input signal uSHW
which is held for 15 minutes, meaning that, when enabled,
the mode remains active for at least 15 minutes and, when
disabled, the mode cannot be enabled again for at least 15
minutes. The enable signal should be computed externally based on a
schedule (to lock out the system during off-hours), ideally in
conjunction with the number of requests or any other signal
representative of the load.
When enabled,
QReqHotWat_flow) combined with the operation of
a thermostatic mixing valve used to mix down the temperature of hot
water leaving the domestic hot water heat exchanger to the
temperature distributed to fixtures (parameter
THotWatSup_nominal) using domestic cold water at the
cold water temperature (input TColWat). The desired
water flow rate leaving the thermostatic mixing valve is determined
according to the following equation:
QReqHotWat_flow = ṁ cp
(THotWatSup_nominal - TColWat)