This model simulates parallel connected cooling tower subsystem with a bypass valve.
The bypass valve is controlled to enforce that the leaving
condenser water temperature does not drop below the minimum
temperature TMin.
By default, the condenser water setpoint is the ambient wet bulb
temperature TWetBul plus the approach temperature
dTApp.
Inside the model, a cooling tower fan speed controller is also implemented to maintain the condenser water at its setpoint.
dp_fixed = 0 for the bypass valve because the
pressure drop in this leg will be significantly less than the
cooling towers.riseTime for the valve signal filters.use_inputFilter = false
for shut-off valve in cooling tower. This avoids a sharp rise in
pressure near t=35 seconds.