Variable air volume flow system of MIT building with CO2 control
and continuous time control for static pressure reset
This examples demonstrates the implementation of CO2
control for a variable air volume flow system. Each room has a
CO2 source. Depending on the CO2
concentrations, the air dampers in the room open or close. The
supply and return fans are controlled to provide a constant static
pressure.
Note that this example does not control the room temperature and
the heat flow through the building envelope. It only implements the
CO2 source and the damper and fan control to maintain a
CO2 concentration in the room below 700 PPM.
Because the building envelope is idealized as having no leakage,
the supply and return fan are controlled so that they both receive
the same control signal. If the return fan were controlled so that
it tracks the volume flow rate of the supply fan, then there would
be multiple solutions for the control signal as the split between
pressure raise of the supply fan and pressure raise of the return
fan is arbitrary.
Contents
- July 12, 2019, by Michael Wetter:
Simplified computation of on/off signal. Used slew rate limiter for
fan control signal rather than 2nd order filter, as this reduces
computing time in JModelica by a factor of two.
- January 20, 2017, by Michael Wetter:
Changed the fan control so that they have a control signal of
exactly zero if the setpoint for the duct static pressure is zero.
This leads to about a four times faster simulation as previously, a
very small control signal was received by the fan during the night
hours.
This is for #628.
- March 22, 2016, by Michael Wetter:
Changed the fan model to use pressure as an input, which makes the
model simulate twenty times faster.
- January 22, 2016, by Michael Wetter:
Corrected type declaration of pressure difference. This is for
#404.
Generated at 2026-04-14T18:18:34Z by OpenModelicaOpenModelica 1.26.3 using
GenerateDoc.mos