This block computes the supply air temperature set point based
on the actual operating mode. The default set point values are
taken from the control sequence VAV 2A2-21232 of the
Sequences of Operation for Common HVAC Systems (ASHRAE,
2006).
| Operating mode | Set point value [C] |
|---|---|
| Occupied | 12 |
| Unoccupied off | 12 |
| Unoccupied, night set back | 35 |
| Unoccupied, warm-up | 35 |
| Unoccupied, pre-cool | 12 |
| Safety | 7 |
ASHRAE. Sequences of Operation for Common HVAC Systems. ASHRAE, Atlanta, GA, 2006.