The CHP plant switches between six possible operating modes depending on the current mode, control signals and plant boundary conditions. The regular transition between them is as follows:
From the off mode:
avaSig becomes
true.From the stand-by mode:
runSig becomes
true.avaSig becomes false, the CHP will
automatically change to the off mode.From the pump-on mode:
mWat_flow is greater than the minimum
mWatMin_flow.runSig becomes false, the CHP will
automatically change to the off mode.From the warm-up mode:
warmUpByTimeDelay is true) or when the engine
temperature TEng becomes higher than the nominal
temperature TEngNom (if warmUpByTimeDelay
is false).runSig becomes false or if the water flow rate
mWat_flow becomes less than the minimum
mWatMin_flow, the CHP will automatically change to the
cool-down mode.From the normal mode:
runSig becomes false or if the water
flow rate mWat_flow becomes less than the minimum
mWatMin_flow.From the cool-down mode:
avaSig is true, the CHP will
change to the stand-by mode; else, it will change to the off
mode.coolDownOptional is false), the plant has to complete
the cool-down period before it can be reactivated. If the CHP has
the optional cool-down configuration (if
coolDownOptional is true), the plant may imediatelly
change to the warm-up mode if it gets reactivated (runSig=
true).