This model validates the model Buildings.Fluid.DXSystems.Cooling.AirSource.SingleSpeed.
The difference in results of TOut and XOut at the beginning and end of the simulation is because the mass flow rate is zero. For zero mass flow rate, EnergyPlus assumes steady state condition, whereas the Modelica model is a dynamic model and hence the properties at the outlet are equal to the state variables of the model.
The EnergyPlus results were generated using the example file
DXCoilSystemAuto.idf from EnergyPlus 7.1, with a
nominal cooling capacity of 10500 Watts instead of using
autosizing. This allowed to have a part load ratio of one.
Note that EnergyPlus mass fractions (X) are in mass
of water vapor per mass of dry air, whereas Modelica uses the total
mass as a reference. Hence, the EnergyPlus values are corrected by
dividing them by 1+X.
| Name | Description |
|---|---|
|
|
Medium model |
sinSpeDX from TConIn to
TOut.Modelica.Fluid.System to address issue
#311.