Calculates UA/Cp of the coil
This model calculates the UA/cp value and the
bypass factor of the coil from the nominal inlet and outlet air
properties.
For a heat exchanger where one medium changes phase, the
NTU-ε relation is
ε = 1 - exp(-NTU) =
1-exp(-UA ⁄ cp ⁄ ṁ).
Since the bypass factor b is defined as b=1-ε, one
can write
b = exp(-UA ⁄
cp ⁄ ṁ)
and, hence,
UA ⁄ cp = -
ṁ log(b).