Horizontal layer that is used to model a U-tube borehole heat exchanger. This model combines three models, each simulating a different aspect of a borehole heat exchanger.
The instance pipFil computes the heat transfer in
the pipes and the filling material. This computation is done using
the model
Buildings.Fluid.Geothermal.Boreholes.BaseClasses.HexInternalElement.
The instance soi computes transient and steady
state heat transfer in the soil using a vertical cylinder. The
computation is done using the model Buildings.HeatTransfer.Conduction.SingleLayerCylinder.
The model TBouCon computes the far-field
temperature boundary condition, i.e., the temperature at the outer
surface of the above cylindrical heat transfer computation. The
computation is done using the model
Buildings.Fluid.Geothermal.Boreholes.BaseClasses.SingleUTubeBoundaryCondition.
| Name | Description |
|---|---|
|
|
Medium in the component |
homotopyInitialization to a constant.B0 and B1.
Updated hyperlinks in the documentation.show_V_flow.