This model validates the model Buildings.Fluid.HeatExchangers.CoolingTowers.Merkel by comparing against results obtained from EnergyPlus.
The EnergyPlus results were obtained using the example file
CoolingTower:VariableSpeed, with the cooling tower
evaluated as the CoolingTower:VariableSpeed:Merkel
model from EnergyPlus.
The difference in results of the cooling tower's leaving water
temperature (tow.TLvg and TLvg.EP) during
the middle and end of the simulation is because the mass flow rate
is zero. For zero mass flow rate, EnergyPlus assumes a steady state
condition, whereas the Modelica model is a dynamic model and hence
the properties at the outlet are equal to the state variables of
the model.
| Name | Description |
|---|---|
|
|
Air medium model |
|
|
Water medium model |
TAirInWB_nominal and added
intermediate equations from E+ to model.