This sequence conducts calculations of the minimum outdoor airflow rate at the zone level. It gives outputs below.
VDesPopBreZon_flow.VDesAreBreZon_flow.yDesPriOutAirFra.VUncOutAir_flow.
This flow rate is calculated based on: occupancy (if there is
occupancy sensor) or design occupancy (if there is no occupancy
sensor), and air distribution effectiveness (warm or cool
air).yPriOutAirFra.VPriAir_flow.The calculation is done using the steps below.
Compute the required breathing zone outdoor airflow using the following components.
VDesAreBreZon_flow.VDesPopBreZon_flow.The number of occupant in the zone can be retrieved directly
from occupancy sensor (nOcc) if the sensor exists, or
using the default occupant density (occDen) and
multiplying it with zone area (AFlo). The occupant
density can be found from Table 6.2.2.1 in ASHRAE Standard
62.1-2013. For design purpose, use the design zone population
(desZonPop) to determine the minimum requirement at
the ventilation-design condition.
Compute the zone air-distribution effectiveness. Table 6.2.2.2
in ASHRAE 62.1-2013 lists some typical values for setting the
effectiveness. Depending on difference between zone space
temperature TZon and discharge air temperature (after
the reheat coil) TDis, Warm-air effectiveness
zonDisEffHea or Cool-air effectiveness
zonDisEffCoo should be applied.
Compute the required zone outdoor airflow
zonOutAirRate. If the zone is in any mode other than
occupied mode (uReqOutAir=false) or if the zone has
window switches and the window is open (uWin=true),
set zonOutAirRate = 0. Otherwise, the required zone
outdoor airflow zonOutAirRate shall be calculated as
follows:
nOcc > 0), or if
there is no occupancy sensor (have_occSen = false):
zonOutAirRate = (breZonAre+breZonPop)/disEffCoo.zonOutAirRate =
(breZonAre+breZonPop)/disEffHea.nOcc=0):
zonOutAirRate = breZonAre/disEffCoo.zonOutAirRate =
breZonAre/disEffHea.Compute the outdoor air fraction for the zone
yPriOutAirFra as follows. Set the zone outdoor air
fraction to
yPriOutAirFra = zonOutAirRate/VPriAir_flow
where, VPriAir_flow is the maximum between the
measured discharge air flow rate from the zone VAV box
VDis_flow and 0.1% of AHU level design uncorrected
minimum outdoor airflow rate VUncOut_flow_nominal. For
design purpose, the design zone outdoor air fraction
yDesPriOutAirFra is
yDesPriOutAirFra = desZonOutAirRate/minZonPriFlo
where minZonPriFlo is the minimum expected zone
primary flow rate and desZonOutAirRate is the required
design zone outdoor airflow rate.
ANSI/ASHRAE Standard 62.1-2013, Ventilation for Acceptable Indoor Air Quality.
Stanke, D., 2010. Dynamic Reset for Multiple-Zone Systems. ASHRAE Journal, March 2010.
min attribute of desZonPop to
zero, and used the expression as a default value. This was done
because the expression involves the zone floor area, which is, if
obtained from Spawn, a non-literal value.fill when assigning the
unit attribute.each.cooCtrlSig input with TZon and
TDis inputs to check if cool or warm air distribution
effectiveness should be applied. Applied hysteresis to avoid rapid
change.