Single zone VAV AHU economizer control sequence that calculates outdoor and return air damper positions based on ASHRAE Guidline 36, PART 5 sections: P.4.d, P.5, P.9, P.3.b, A.17.
The sequence consists of three subsequences.
damLim computes the damper
position limits to satisfy outdoor air requirements. See
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.SingleZone.VAV.Economizers.Subsequences.Limits
for a description.enaDis enables or disables the
economizer based on outdoor temperature and optionally enthalpy,
and based on the supply fan status, freeze protection stage and
zone state. See
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.SingleZone.VAV.Economizers.Subsequences.Enable
for a description.mod modulates the outdoor and
return damper position to track the supply air temperature setpoint
for heating, subject to the limits of the damper positions that
were computed in the above two blocks. See
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.SingleZone.VAV.Economizers.Subsequences.Modulation
for a description.