This atomic sequence sets the minimum outdoor airflow setpoint for compliance with the ventilation rate procedure of ASHRAE 62.1-2013. The implementation is according to ASHRAE Guidline 36 (G36), PART 5.P.4.b, PART 5.B.2.b, PART3.1-D.2.a.
breZonbreZonAre = AFlo*VOutPerAre_flow.breZonPop = occCou*VOutPerPer_flow.The number of occupant occCou could be retrieved
directly from occupancy sensor nOcc if the sensor
exists (have_occSen=true), or using the default
occupant density occDen to find it
AFlo*occDen. The occupant density can be found from
Table 6.2.2.1 in ASHRAE Standard 62.1-2013.
zonDisEffTable 6.2.2.2 in ASHRAE 62.1-2013 lists some typical values for
setting the effectiveness. Depending on difference between zone
space temperature TZon and supply air temperature
TDis, Warm-air effectiveness zonDisEffHea
or Cool-air effectiveness zonDisEffCoo should be
applied.
zonOutAirRateFor each zone in any mode other than occupied mode and for zones
that have window switches and the window is open,
zonOutAirRate shall be zero. Otherwise, the required
zone outdoor airflow zonOutAirRate shall be calculated
as follows:
zonOutAirRate =
(breZonAre+breZonPop)/disEffCoo.zonOutAirRate =
(breZonAre+breZonPop)/disEffHeazonOutAirRate =
breZonAre/disEffCoozonOutAirRate =
breZonAre/disEffHeaFor the single zone system, the required minimum outdoor airflow
setpoint VOutMinSet_flow equals to the
zonOutAirRate.
nOcc conditionally removable,
as it is for the multizone implementation. This is for issue
1270.cooCtrlSig input with TZon and
TDis inputs to check if cool or warm air distribution
effectiveness should be applied. Applied hysteresis to avoid rapid
change.