Controller for terminal box of VAV system with reheat according
to ASHRAE Guideline 36, Part 5.E. It outputs damper position
yDam, hot water valve position yVal, AHU
cooling supply temperature setpoint reset request
yZonTemResReq, and static pressure setpoint reset
request yZonPreResReq.
The sequence consists of four subsequences.
The subsequence is implementd according to Part 5.B.5. The
measured zone temperature TZon, zone setpoints
temperatures TZonHeaSet and TZonCooSet
are inputs to the block conHeaLoo and
conCooLoo to generate the control loop signal.
This sequence sets the active maximum and minimum airflow
according to Part 5.E.3-5. Depending on operation modes
uOpeMod, it sets the airflow rate limits for cooling
and heating supply. See
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.TerminalUnits.Reheat.SetPoints.ActiveAirFlow.
This sequence sets the damper and valve position for VAV reheat
terminal unit. The implementation is according to Part 5.E.6.
According to heating and cooling control loop signal, it calculates
the discharge air temperature setpoint TDisHeaSet.
Along with the defined maximum and minimum airflow, measured zone
temperature, the sequence outputs yDam,
yVal, TDisHeaSet and discharge airflow
rate setpoint VDisSet_flow. See
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.TerminalUnits.Reheat.DamperValves.
According to Part 5.E.9, this sequence outputs the system reset
requests, i.e. cooling supply air temperature reset requests
yZonTemResReq, static pressure reset requests
yZonPreResReq, hot water reset requests
yHeaValResReq, and the boiler plant reset requests
yHeaPlaReq. See
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.TerminalUnits.Reheat.SystemRequests.
yHeaValResReq and
yHeaPlaReq for requests to heating plant.