This model validates the model Buildings.Templates.Components.Chillers.Compression in a configuration in which the chiller is exposed to a constant differential pressure and a varying return temperature.
The chiller model is configured to represent either an air-cooled
chiller (component chiAirCoo) or a water-cooled
chiller (component chiWatCoo).
Regarding the parameterization logic described in the documentation of
Buildings.Templates.Components.Chillers.Compression:
The air-cooled chiller component is parameterized using the
specified design conditions (datChiAirCoo.use_datDes=true)
and a direct assignment of the performance curves
per.capFunT, per.EIRFunT and per.EIRFunPLR.
The water-cooled chiller component is parameterized using the
rating conditions specified in the redeclared performance record
(datChiWatCoo.use_datDes=false) and no direct assignment
of the design parameters.
| Name | Description |
|---|---|
| MediumLiq | CHW or CW medium |
| MediumAir | Air medium |