Plant enable
The plant is enabled when it has been disabled for at least the
duration dtRun and:
- Number of plant requests > number of ignored requests
nReqIgn, and
- For cooling systems: outdoor air temperature >
outdoor air lockout temperature
TOutLck, and
- For heating systems: outdoor air temperature <
outdoor air lockout temperature
TOutLck, and
- The enable schedule is active.
The plant is disabled when it has been enabled for at least the
duration dtRun and:
- Number of plant requests ≤ number of ignored requests
nReqIgn for at least the duration dtReq,
or
- For cooling systems: outdoor air temperature <
outdoor air lockout temperature
TOutLck minus
hysteresis dTOutLck, or
- For heating systems: outdoor air temperature >
outdoor air lockout temperature
TOutLck plus
hysteresis dTOutLck, or
- The plant enable schedule is inactive.
- March 29, 2024, by Antoine Gautier:
First implementation.
Generated at 2026-04-15T18:18:36Z by OpenModelicaOpenModelica 1.26.3 using