The HW minimum flow bypass valve is modulated based on a reverse acting control loop to maintain the primary HW flow rate at setpoint. The setpoint is calculated as described in Buildings.Templates.Plants.Controls.MinimumFlow.Setpoint using the number of units commanded on in heating mode at each stage.
When using isolation valve command signals
(have_valInlIso=true or
have_valOutIso=true): When any HW isolation valve is
commanded open, the HW bypass valve control loop is enabled. The
valve is opened 100 % otherwise. When enabled, the HW
bypass valve loop shall be biased to start with the valve
100 % open.
Otherwise (have_valInlIso=false and
have_valOutIso=false):
The CHW minimum flow bypass valve is modulated based on a reverse acting control loop to maintain the primary CHW flow rate at setpoint. The setpoint is calculated as described in Buildings.Templates.Plants.Controls.MinimumFlow.Setpoint using the number of units commanded on in cooling mode at each stage.
When using isolation valve command signals
(have_valInlIso=true or
have_valOutIso=true): When any CHW isolation valve is
commanded open, the CHW bypass valve control loop is enabled. The
valve is opened 100 % otherwise. When enabled, the CHW
bypass valve loop shall be biased to start with the valve
100 % open.
Otherwise (have_valInlIso=false and
have_valOutIso=false):