PID controller with enable signal
This is an update of Buildings.Controls.OBC.CDL.Reals.PIDWithReset
with an additional enable signal provided as a Boolean input.
- When enabled, the output of the controller is identical to
Buildings.Controls.OBC.CDL.Reals.PIDWithReset,
and the integral term is reset to
y_reset at enable
time.
- When disabled, the output of the controller is set to
y_neutral and the setpoint is overridden by the
measurement signal in order to avoid time integration of the
control error.
- March 29, 2024, by Antoine Gautier:
First implementation.