This class implements the sequence of operation for plants with air-to-water heat pumps. It is based on the controller Buildings.Templates.Plants.Controls.HeatPumps.AirToWater.
The control sequence requires the following external input points in addition to those already included in the HP plant template.
TOut: AI signal with a
dimensionality of zerodpHeaWatRem: AI signal with a dimensionality of one,
the number of remote sensors is specified by the parameter
nSenDpHeaWatRem.dpChiWatRem – only for heating and cooling plants: AI
signal with a dimensionality of one, the number of remote sensors
is specified by the parameter nSenDpChiWatRem.busAirHan[:] or
busEquZon[:], with a dimensionality of one
bus(AirHan|EquZon)[:].reqPlaHeaWat: AI
signal (Integer), with a dimensionality of onebus(AirHan|EquZon)[:].reqResHeaWat: AI
signal (Integer), with a dimensionality of onebus(AirHan|EquZon)[:].reqPlaChiWat: AI signal
(Integer), with a dimensionality of onebus(AirHan|EquZon)[:].reqResChiWat: AI signal
(Integer), with a dimensionality of one